Vulnerability Monitor

The vendors, products, and vulnerabilities you care about

CVE-2016-8562


A vulnerability has been identified in SIMATIC CP 1543-1 (All versions < V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Under special conditions it was possible to write SNMP variables on port 161/udp which should be read-only and should only be configured with TIA-Portal. A write to these variables could reduce the availability or cause a denial-of-service.


Published

2016-11-18T21:59:02.033

Last Modified

2025-04-12T10:46:40.837

Status

Deferred

Source

[email protected]

Severity

CVSSv3.1: 7.5 (HIGH)

CVSSv2 Vector

AV:N/AC:M/Au:S/C:N/I:N/A:P

  • Access Vector: NETWORK
  • Access Complexity: MEDIUM
  • Authentication: SINGLE
  • Confidentiality Impact: NONE
  • Integrity Impact: NONE
  • Availability Impact: PARTIAL
Exploitability Score

6.8

Impact Score

2.9

Weaknesses
  • Type: Primary
    NVD-CWE-noinfo

Affected Vendors & Products
Type Vendor Product Version/Range Vulnerable?
Operating System siemens simatic_cp_1543-1_firmware < 2.0.28 Yes
Hardware siemens simatic_cp_1543-1 - No
Operating System siemens siplus_net_cp_1543-1_firmware < 2.0.28 Yes
Hardware siemens siplus_net_cp_1543-1 - No

References