An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability.Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0001 Fault Type: Non-User Description: A fault state can be triggered by setting the NVRAM/memory module user program mismatch bit (S2:9) when a memory module is NOT installed.
2018-04-05T21:29:00.633
2024-11-21T03:12:50.790
Modified
CVSSv3.1: 9.8 (CRITICAL)
AV:N/AC:L/Au:N/C:P/I:P/A:P
10.0
6.4
| Type | Vendor | Product | Version/Range | Vulnerable? |
|---|---|---|---|---|
| Operating System | rockwellautomation | micrologix_1400_b_firmware | ≤ 21.2 | Yes |
| Hardware | rockwellautomation | micrologix_1400 | - | No |