An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG or RUN Description: The value 0xffffffff is considered NaN for the Float data type. When a float is set to this value and used in the PLC, a fault is triggered. NOTE: This is not possible through RSLogix.


Published

2018-04-05T21:29:01.037

Last Modified

2024-11-21T03:12:51.443

Status

Modified

Source

[email protected]

Severity

CVSSv3.0: 10.0 (CRITICAL)

CVSSv2 Vector

AV:N/AC:L/Au:N/C:P/I:P/A:P

  • Access Vector: NETWORK
  • Access Complexity: LOW
  • Authentication: NONE
  • Confidentiality Impact: PARTIAL
  • Integrity Impact: PARTIAL
  • Availability Impact: PARTIAL
Exploitability Score

10.0

Impact Score

6.4

Weaknesses
  • Type: Primary
    NVD-CWE-noinfo

Affected Vendors & Products
Type Vendor Product Version/Range Vulnerable?
Operating System rockwellautomation micrologix_1400_b_firmware ≤ 21.2 Yes
Hardware rockwellautomation micrologix_1400 - No