Vulnerability Monitor

The vendors, products, and vulnerabilities you care about

CVE-2018-13805


A vulnerability has been identified in SIMATIC ET 200SP Open Controller (All versions >= V2.0 and < V2.1.6), SIMATIC S7-1500 Software Controller (All versions >= V2.0 and < V2.5), SIMATIC S7-1500 incl. F (All versions >= V2.0 and < V2.5). An attacker can cause a denial-of-service condition on the network stack by sending a large number of specially crafted packets to the PLC. The PLC will lose its ability to communicate over the network. This vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no privileges and no user interaction. An attacker could use this vulnerability to compromise availability of the network connectivity. At the time of advisory publication no public exploitation of this vulnerability was known.


Published

2018-10-10T17:29:04.170

Last Modified

2024-11-21T03:48:05.947

Status

Modified

Source

[email protected]

Severity

CVSSv3.0: 7.5 (HIGH)

CVSSv2 Vector

AV:N/AC:L/Au:N/C:N/I:N/A:P

  • Access Vector: NETWORK
  • Access Complexity: LOW
  • Authentication: NONE
  • Confidentiality Impact: NONE
  • Integrity Impact: NONE
  • Availability Impact: PARTIAL
Exploitability Score

10.0

Impact Score

2.9

Weaknesses
  • Type: Primary
    CWE-400

Affected Vendors & Products
Type Vendor Product Version/Range Vulnerable?
Operating System siemens simatic_et_200sp_firmware ≥ 2.0 Yes
Hardware siemens simatic_et_200sp - No
Operating System siemens simatic_s7-1500_firmware < 2.5 Yes
Hardware siemens simatic_s7-1500 - No
Operating System siemens simatic_s7-1500f_firmware < 2.5 Yes
Hardware siemens simatic_s7-1500f - No

References