Vulnerability Monitor

The vendors, products, and vulnerabilities you care about

CVE-2018-13811


A vulnerability has been identified in SIMATIC STEP 7 (TIA Portal) (All Versions < V15.1). Password hashes with insufficient computational effort could allow an attacker to access to a project file and reconstruct passwords. The vulnerability could be exploited by an attacker with local access to the project file. No user interaction is required to exploit the vulnerability. The vulnerability could allow the attacker to obtain certain passwords from the project. At the time of advisory publication no public exploitation of this vulnerability was known.


Published

2018-12-13T16:29:00.257

Last Modified

2024-11-21T03:48:07.027

Status

Modified

Source

[email protected]

Severity

CVSSv3.0: 5.5 (MEDIUM)

CVSSv2 Vector

AV:L/AC:L/Au:N/C:P/I:N/A:N

  • Access Vector: LOCAL
  • Access Complexity: LOW
  • Authentication: NONE
  • Confidentiality Impact: PARTIAL
  • Integrity Impact: NONE
  • Availability Impact: NONE
Exploitability Score

3.9

Impact Score

2.9

Weaknesses
  • Type: Secondary
    CWE-916
  • Type: Primary
    CWE-200

Affected Vendors & Products
Type Vendor Product Version/Range Vulnerable?
Application siemens simatic_step_7_\(tia_portal\) < 15.1 Yes

References