Vulnerability Monitor

The vendors, products, and vulnerabilities you care about

CVE-2018-13815


A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6). An attacker could exhaust the available connection pool of an affected device by opening a sufficient number of connections to the device. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. The vulnerability, if exploited, could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication no public exploitation of this vulnerability was known.


Published

2018-12-13T16:29:00.383

Last Modified

2024-11-21T03:48:07.740

Status

Modified

Source

[email protected]

Severity

CVSSv3.0: 7.5 (HIGH)

CVSSv2 Vector

AV:N/AC:L/Au:N/C:N/I:N/A:P

  • Access Vector: NETWORK
  • Access Complexity: LOW
  • Authentication: NONE
  • Confidentiality Impact: NONE
  • Integrity Impact: NONE
  • Availability Impact: PARTIAL
Exploitability Score

10.0

Impact Score

2.9

Weaknesses
  • Type: Secondary
    CWE-410
  • Type: Primary
    CWE-400

Affected Vendors & Products
Type Vendor Product Version/Range Vulnerable?
Operating System siemens simatic_s7-1200_firmware - Yes
Hardware siemens simatic_s7-1200 - No
Operating System siemens simatic_s7-1500_firmware < 2.6 Yes
Hardware siemens simatic_s7-1500 - No

References