A vulnerability has been identified in SIMATIC S7-400 (incl. F) CPU hardware version 4.0 and below (All versions), SIMATIC S7-400 (incl. F) CPU hardware version 5.0 (All firmware versions < V5.2), SIMATIC S7-400H CPU hardware version 4.5 and below (All versions). The affected CPUs improperly validate S7 communication packets which could cause a Denial-of-Service condition of the CPU. The CPU will remain in DEFECT mode until manual restart.
2018-05-16T17:29:00.387
2024-11-21T04:07:35.003
Modified
CVSSv3.0: 7.5 (HIGH)
AV:N/AC:L/Au:N/C:N/I:N/A:P
10.0
2.9
Type | Vendor | Product | Version/Range | Vulnerable? |
---|---|---|---|---|
Operating System | siemens | simatic_s7-400_firmware | ≤ 4.0 | Yes |
Hardware | siemens | simatic_s7-400 | - | No |
Operating System | siemens | simatic_s7-400_firmware | < 5.2 | Yes |
Hardware | siemens | simatic_s7-400 | - | No |
Operating System | siemens | simatic_s7-400h_firmware | ≤ 4.5 | Yes |
Hardware | siemens | simatic_s7-400h | - | No |