Vulnerability Monitor

The vendors, products, and vulnerabilities you care about

CVE-2019-6576


A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). An attacker with network access to affected devices could potentially obtain a TLS session key. If the attacker is able to observe TLS traffic between a legitimate user and the device, then the attacker could decrypt the TLS traffic. The security vulnerability could be exploited by an attacker who has network access to the web interface of the device and who is able to observe TLS traffic between legitimate users and the web interface of the affected device. The vulnerability could impact the confidentiality of the communication between the affected device and a legitimate user. At the time of advisory publication no public exploitation of the security vulnerability was known.


Security Impact Summary

This vulnerability carries a HIGH severity rating with a CVSS v3.1 score of 7.5, indicating it can be exploited remotely over the network with relatively low complexity without requiring user interaction and does not require pre-existing privileges . The vulnerability impacts confidentiality (data exposure), for affected systems. Impacting 22 products from siemens, from siemens, from siemens and 19 others, organizations running these solutions should prioritize assessment and patching.

Historical Context

First disclosed in 2019, this vulnerability was reported during a period defined by widespread IoT adoption challenges, mobile security concerns, and the emergence of advanced persistent threat (APT) techniques. Contemporary mitigation strategies focused on secure development practices and third-party component vetting.


Published

2019-05-14T20:29:04.560

Last Modified

2024-11-21T04:46:44.130

Status

Modified

Source

[email protected]

Severity

CVSSv3.0: 7.5 (HIGH)

CVSSv2 Vector

AV:N/AC:L/Au:N/C:P/I:N/A:N

  • Access Vector: NETWORK
  • Access Complexity: LOW
  • Authentication: NONE
  • Confidentiality Impact: PARTIAL
  • Integrity Impact: NONE
  • Availability Impact: NONE
Exploitability Score

10.0

Impact Score

2.9

Weaknesses
  • Type: Secondary
    CWE-310
  • Type: Primary
    CWE-310

Affected Vendors & Products
Type Vendor Product Version/Range Vulnerable?
Operating System siemens simatic_hmi_comfort_panels_firmware < 15.1 Yes
Hardware siemens simatic_hmi_comfort_panels - No
Operating System siemens simatic_hmi_comfort_outdoor_panels_firmware < 15.1 Yes
Hardware siemens simatic_hmi_comfort_outdoor_panels - No
Operating System siemens simatic_hmi_ktp_mobile_panels_ktp400f_firmware < 15.1 Yes
Hardware siemens simatic_hmi_ktp_mobile_panels_ktp400f - No
Operating System siemens simatic_hmi_ktp_mobile_panels_ktp700_firmware < 15.1 Yes
Hardware siemens simatic_hmi_ktp_mobile_panels_ktp700 - No
Operating System siemens simatic_hmi_ktp_mobile_panels_ktp700f_firmware < 15.1 Yes
Hardware siemens simatic_hmi_ktp_mobile_panels_ktp700f - No
Operating System siemens simatic_hmi_ktp_mobile_panels_ktp900_firmware < 15.1 Yes
Hardware siemens simatic_hmi_ktp_mobile_panels_ktp900 - No
Operating System siemens simatic_hmi_ktp_mobile_panels_ktp900f_firmware < 15.1 Yes
Hardware siemens simatic_hmi_ktp_mobile_panels_ktp900f - No
Application siemens simatic_wincc_\(tia_portal\) < 15.1 Yes
Application siemens simatic_wincc_runtime < 15.1 Yes
Application siemens simatic_wincc_runtime < 15.1 Yes
Operating System siemens simatic_hmi_tp_firmware * Yes
Hardware siemens simatic_hmi_tp - No
Operating System siemens simatic_hmi_mp_firmware * Yes
Hardware siemens simatic_hmi_mp - No
Operating System siemens simatic_hmi_op_firmware * Yes
Hardware siemens simatic_hmi_op - No

References

How SecUtils Interprets This CVE

SecUtils normalizes and enriches National Vulnerability Database (NVD) records by standardizing vendor and product identifiers, aggregating vulnerability metadata from both NVD and MITRE sources, and providing structured context for security teams. For siemens's affected products, we extract Common Platform Enumeration (CPE) data, Common Weakness Enumeration (CWE) classifications, CVSS severity metrics, and reference data to enable rapid vulnerability prioritization and asset correlation. This record contains no exploit code, proof-of-concept instructions, or attack methodologies—only defensive intelligence necessary for patch management, risk assessment, and security operations.