Vulnerability Monitor

The vendors, products, and vulnerabilities you care about

CVE-2019-6831


A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in BMXNOR0200H Ethernet / Serial RTU module (all firmware versions), which could cause disconnection of active connections when an unusually high number of IEC 60870- 5-104 packets are received by the module on port 2404/TCP.


Published

2019-09-17T20:15:12.343

Last Modified

2024-11-21T04:47:14.383

Status

Modified

Source

[email protected]

Severity

CVSSv3.1: 8.6 (HIGH)

CVSSv2 Vector

AV:N/AC:L/Au:N/C:N/I:N/A:P

  • Access Vector: NETWORK
  • Access Complexity: LOW
  • Authentication: NONE
  • Confidentiality Impact: NONE
  • Integrity Impact: NONE
  • Availability Impact: PARTIAL
Exploitability Score

10.0

Impact Score

2.9

Weaknesses
  • Type: Secondary
    CWE-754
  • Type: Primary
    CWE-754

Affected Vendors & Products
Type Vendor Product Version/Range Vulnerable?
Operating System schneider-electric bmxnor0200h_firmware * Yes
Hardware schneider-electric bmxnor0200h - No

References