Vulnerability Monitor

The vendors, products, and vulnerabilities you care about

CVE-2020-27736


A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the read memory.


Published

2021-04-22T21:15:09.250

Last Modified

2024-11-21T05:21:43.303

Status

Modified

Source

[email protected]

Severity

CVSSv3.1: 6.5 (MEDIUM)

CVSSv2 Vector

AV:N/AC:M/Au:N/C:P/I:N/A:P

  • Access Vector: NETWORK
  • Access Complexity: MEDIUM
  • Authentication: NONE
  • Confidentiality Impact: PARTIAL
  • Integrity Impact: NONE
  • Availability Impact: PARTIAL
Exploitability Score

8.6

Impact Score

4.9

Weaknesses
  • Type: Secondary
    CWE-170
  • Type: Primary
    CWE-125

Affected Vendors & Products
Type Vendor Product Version/Range Vulnerable?
Application siemens nucleus_net * Yes
Application siemens nucleus_readystart_v3 < 2017.02.3 Yes
Application siemens nucleus_readystart_v4 < 4.1.0 Yes
Application siemens nucleus_source_code - Yes
Operating System siemens simotics_connect_400_firmware < 0.5.0.0 Yes
Hardware siemens simotics_connect_400 - No

References