A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS response parsing functionality does not properly validate various length and counts of the records. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the memory past the allocated structure.
2021-04-22T21:15:09.280
2024-11-21T05:21:43.447
Modified
CVSSv3.1: 6.5 (MEDIUM)
AV:N/AC:M/Au:N/C:P/I:N/A:P
8.6
4.9
Type | Vendor | Product | Version/Range | Vulnerable? |
---|---|---|---|---|
Operating System | siemens | simotics_connect_400_firmware | < 0.5.0.0 | Yes |
Hardware | siemens | simotics_connect_400 | - | No |
Application | siemens | nucleus_net | * | Yes |
Application | siemens | nucleus_readystart_v3 | < 2017.02.3 | Yes |
Application | siemens | nucleus_readystart_v4 | < 4.1.0 | Yes |
Application | siemens | nucleus_source_code | - | Yes |