A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones.
2021-02-09T18:15:34.590
2024-11-21T05:22:42.130
Modified
CVSSv3.1: 6.5 (MEDIUM)
AV:N/AC:L/Au:N/C:N/I:P/A:N
10.0
2.9
Type | Vendor | Product | Version/Range | Vulnerable? |
---|---|---|---|---|
Application | siemens | capital_vstar | * | Yes |
Application | siemens | nucleus_net | < 5.2 | Yes |
Application | siemens | nucleus_source_code | * | Yes |
Application | siemens | pluscontrol_1st_gen | * | Yes |
Application | siemens | nucleus_readystart | < 2012.12 | Yes |
Hardware | arm | arm | - | No |
Hardware | mips | mips | - | No |
Hardware | powerpc_project | powerpc | - | No |