A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). When the controller receives a specific BACnet protocol packet, an exception causes the BACnet communication function to go into a “out of work” state and could result in the controller going into a “factory reset” state.
2022-05-10T11:15:07.840
2024-11-21T06:26:23.437
Modified
CVSSv3.1: 7.5 (HIGH)
AV:N/AC:L/Au:N/C:N/I:N/A:P
10.0
2.9
Type | Vendor | Product | Version/Range | Vulnerable? |
---|---|---|---|---|
Operating System | siemens | desigo_dxr2_firmware | < 01.21.142.5-22 | Yes |
Hardware | siemens | desigo_dxr2 | - | No |
Operating System | siemens | desigo_pxc3_firmware | < 01.21.142.4-18 | Yes |
Hardware | siemens | desigo_pxc3 | - | No |
Operating System | siemens | desigo_pxc4_firmware | < 02.20.142.10-10884 | Yes |
Hardware | siemens | desigo_pxc4 | - | No |
Operating System | siemens | desigo_pxc5_firmware | < 02.20.142.10-10884 | Yes |
Hardware | siemens | desigo_pxc5 | - | No |