A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
2023-07-26T06:15:10.220
2024-11-21T07:35:35.383
Modified
CVSSv3.1: 7.5 (HIGH)
Type | Vendor | Product | Version/Range | Vulnerable? |
---|---|---|---|---|
Operating System | hitachienergy | rtu500_firmware | 13.3.1 | Yes |
Operating System | hitachienergy | rtu500_firmware | 13.3.2 | Yes |
Operating System | hitachienergy | rtu500_firmware | 13.3.3 | Yes |
Operating System | hitachienergy | rtu500_firmware | 13.4.1 | Yes |
Hardware | hitachienergy | rtu500 | - | No |