Vulnerability Monitor

The vendors, products, and vulnerabilities you care about

CVE-2022-4608


A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.


Published

2023-07-26T06:15:10.220

Last Modified

2024-11-21T07:35:35.383

Status

Modified

Source

[email protected]

Severity

CVSSv3.1: 7.5 (HIGH)

Weaknesses
  • Type: Secondary
    CWE-787
  • Type: Primary
    CWE-787

Affected Vendors & Products
Type Vendor Product Version/Range Vulnerable?
Operating System hitachienergy rtu500_firmware 13.3.1 Yes
Operating System hitachienergy rtu500_firmware 13.3.2 Yes
Operating System hitachienergy rtu500_firmware 13.3.3 Yes
Operating System hitachienergy rtu500_firmware 13.4.1 Yes
Hardware hitachienergy rtu500 - No

References